| Important technical data, overview |
| Type in accordance with IEC/EN 61496 |
4 |
| SIL in accordance with IEC 61508 and SILCL in accordance with IEC/EN 62061 |
3 |
| Performance Level (PL) in accordance with EN ISO 13849-1 |
e |
| Category in accordance with EN ISO 13849 |
4 |
| Range (type-dependent) |
MLD5yy-R /-T: 0.5...70 m MLD5yy-xR /-xT: 20...100 m |
| Profile cross-section |
52 mm x 55 mm |
| Safety-related switching output (OSSD) |
AS-i Safety Interface |
| Connection system |
M12 plug (AS-i Safety) |
| AS-i profile |
S-7.B.1, safe slave |
| Slave address |
1...31, programmable (factory setting = 0) |
| Cycle time in accordance with AS-i specifications |
5 ms |
| Current consumption from AS-i circuit |
50 mA (transmitter), max. 140 mA (receiver, type-dependent) |
| Sensor response time |
25 ms |
| Restart delay time |
100 ms or 500 ms |