General system data
|
| Category in accordance with EN ISO 13849 |
Up to 4 (depending on the category of the upstream protective device) |
| Service life (TM ) in accordance with EN ISO 13849-1 |
On request |
| Number of cycles until 10 % of the components have a failure to danger (B10d)* |
with DC1 (ohmic load) |
125,000 |
| with AC1 (ohmic load) |
125,000 |
| with DC13 (inductive load) |
40,000 (2 A, 24 V) |
| with AC15 (inductive load) |
60,000 (2 A, 24 V) |
| Low load (20% nominal load) |
1,860,000 |
| Supply voltage |
24 V DC ±20 % (via OSSDs of the connected AOPD) |
| Power consumption |
1.5 W (supply via AOPD) |
| Safety-related switching outputs (OSSDs) |
2 relay outputs (changeover) |
| Signal output |
Relay output (NC) |
| Continuous current per current path |
max. 3 A |
| Response time |
10 ms |
| Restart delay time |
20 ms |
| Current consumption (inputs B1 and B3) |
32 mA each |
| Admissible input line resistance |
50 |
| Temperature range, operation |
0...+50 °C |
| Temperature range, storage |
-25...+70 °C |
| Safety class |
II |
| Protection rating |
IP 20 |
| Connection system |
Screw terminals |
| Dimensions (W x H x D) |
17.5 mm x 99 mm x 113.6 mm |
| Mounting |
on 35 mm DIN rail |